Product Details:

  • Product Type Infrared Temperature Sensors
  • Material Metal
  • Function Measuring Temperature
  • Usage Electrical Instruments
  • Accuracy 99.9 %
X

Infrared Temperature Sensors PyroCAN Price And Quantity

  • 10 Unit

Infrared Temperature Sensors PyroCAN Product Specifications

  • Metal
  • Electrical Instruments
  • Measuring Temperature
  • Infrared Temperature Sensors
  • 99.9 %

Infrared Temperature Sensors PyroCAN Trade Information

  • 500 Unit Per Day
  • 1-7 Days
  • All India

Product Description

Sensor Features
  • Non-contact infrared temperature sensor with CAN Bus interface
  • Temperature range: -20C to 1000C
  • Raw CAN protocol
  • Configurable CAN ID and adjustable emissivity setting
  • Not designed or approved for fever detection

General Specifications:

Attribute

Value

Temperature Range

-20C to 1000C

Interface

Raw CAN

Accuracy

1% of reading or 1C, whichever is greater

Repeatability

0.5% of reading or 0.5C, whichever is greater

Emissivity Setting

Adjustable via CAN, 0.2 to 1.0

Response Time, t90

200 ms (90% response)

Spectral Range

8 to 14 m

Supply Voltage

12 to 24 V DC

Supply Current

50 mA max.

CAN Protocol Specifications:

Attribute

Value

Baud Rate

250 kbps

Data Format

8 bytes total:


Bytes 1-4: Object temperature as floating point


Bytes 5-8: Ambient temperature as floating point

Transmit Interval

200 ms

CAN ID Range

ID can be set between 0 and 255 as a 4-byte unsigned integer

Emissivity

Adjustable from 0.2 to 1.0 as a 4-byte floating point

Mechanical Specifications:

Attribute

Value

Construction

Stainless Steel

Dimensions

18 mm diameter x 103 mm long

Thread Mounting

M16 x 1 mm pitch

Cable Length

1m (longer lengths available to order)

Weight with Cable

95 g

Environmental Specifications:

Attribute

Value

Environmental Rating

IP65

Ambient Temperature Range

0C to 90C

Relative Humidity

95% max. non-condensing

 Please note: The given measured spot size contains 90% of the energy detected by the sensor. We normally recommend the target is at least twice as large as the given measured spot for maximum accuracy. Sensors may be used at longer distances than the above diagrams show. There is no maximum measurement distance in clean air; this is because the PyroCAN detects only the wavelengths of infrared radiation that are not absorbed by the atmosphere.


Enter Buying Requirement Details
Email Id
Mobile number